ABB, Maintenance & Diagnostics, Protection Relays

Emax 2 Trip-Unit Navigation: The Fault Record That May Save Hours of Troubleshooting

Real photographed SACE Emax 2 Trip Unit hardware — sample configuration
VIDEO-FIRST ENGINEERING BRIEFING FAYYAZ / FIELD NOTES 13

[fayyaz_youtube id=”U3_adFWOL0o”]

WATCH FIRST · ABB Emax 2 Ekip Touch Measurements Navigation — ABB video manual · Publisher: ABB.

ABB / ENGINEERING IN PRACTICE

A useful alarm tells you what tripped

After an ACB trip, pressing reset too quickly can erase the story the switchboard is trying to tell. An Ekip trip unit should be treated as a diagnostic instrument, not a large green ON button.

SACE Emax 2 Trip Unit product photo
ABB Ekip Touch LSI trip unit component photographed separately; exact model varies with ACB version. Manufacturer reference
THE TAKEAWAY

After an ACB trip, pressing reset too quickly can erase the story the switchboard is trying to tell. An Ekip trip unit should be treated as a diagnostic instrument, not a large green ON button. Practical selection guidance, wiring decisions and a test checklist.

01 / Start with trip cause before any reset

Observe and record fault indication, timestamp, currents and protection cause where the installed unit permits. Separate overload, short-circuit, ground-fault and external-trip paths; the suitable recovery procedure differs for each. A trip caused by protection action is not just a nuisance alarm.

02 / Measure before guessing

The selected Ekip model may show phase electrical measurements and historical events. Compare readings with independent instrumentation and a verified one-line drawing. If the fault recurs at a particular load transition, correlate the ACB log with PLC and energy-meter data before changing settings.

03 / Protect the settings

Record approved settings, access level and revision date. Changes to an LSIG curve must be controlled against the plant selectivity study; a faster downstream fault trip is not necessarily safer if it removes the desired discrimination.

04 / Operator interface detail

Create a simple two-page handover: how to identify a real protection trip and how to escalate. Keep electrician-only actions separate from operator controls. An HMI should show the device fault without encouraging unauthorized reset.

05 / Practical plant result

Detailed trip records can reduce mean time to diagnose if they are backed up and interpreted correctly. No credible field reliability ranking can be inferred from manufacturer videos; report project-specific experience only if actual data exists.

ENGINEER’S REFERENCE TABLE

Key evidenceTrip cause, time, measurements
Important distinctionProtection trip vs remote open command
DocumentSettings log and event history
RiskReset before diagnosis can hide root cause

FAT / COMMISSIONING: WHAT TO VERIFY

  1. Read and record trip information before resetting.
  2. Inspect loads and cabling for the indicated fault class.
  3. Verify with backup/event records and SCADA timestamps.
  4. Obtain authorization before settings changes.
  5. Record corrective work and repeated-trip frequency.

Technical sources and video credits

Independent FAYYAZ Electric technical analysis; figures and options vary with the exact device part number and firmware. This article is not a manufacturer installation procedure.

Video embed availability is controlled by the video owner and YouTube; successful indexing does not guarantee inline playback.


[fayyaz_reviews]